Technical data
Corresponds to DIN DVGW or ÖNORM B5014-3
FWM 33:
Tap output 33 l/min. with 45 °C at 60 °C buffer temperature
Pressure loss module drinking water side:
33 l/min = 580 mbar (5.8 mWs)
15 l/min = 150 mbar (1.5 mWs)
FWM 44:
Tap output 44 l/min. with 45 °C at 60 °C buffer temperature
Pressure loss module drinking water side:
44 l/min = 560 mbar (5.6 mWs)
20 l/min = 160 mbar (1.6 mWs)
Plastic cap H=600 mm, W=400 mm, D=190 mm
Cascadable for greater tap outputs
Scope of delivery
The module is delivered as a whole unit already pre-assembled on a mounting plate and includes:
MicroPlate® plate heat exchanger:
Heating side:
- Speed-controlled high-efficiency pump in buffer circuit with check valve
- Speed-controlled high-efficiency pump for return admixing (limescale protection) with check valve
- Bleed valve (manual)
- Connecting ball valves 3/4“ (FWM 44: 1“) internal thread
Water side:
- Flow meter to determine the current tap quantity
- Check valve
- Defined connection for circulation set
- Flush ball valves DN 15 (1/2") and connecting ball valves 3/4“ (FWM 44: 1“) internal thread according to DIN DVGW or ÖNORM B5014-3
Control system with safety plug:
The components inside the module are already pre-wired.
Control system contains 2 freely available sensors inputs (for poss. connection of the buffer sensors) and an output for the circulation set.
Loosely enclosed:
CAN-Bus line L=10 m for connection with ETA boiler control system
Technical data
Circulation set
Energy-saving pump
10 bar safety valve, protects the lines from too much water pressure
Circulation line connector DN 20 (3/4") external thread. All components relevant to operation, such as e. g. check valve, are already integrated.