Technical data
SP stratified buffer and SPS 600 to 2200
The number and position of the connections is optimised for the ETA hydraulics and control system. The following figures depict a Solar SPS
stratified buffer with a supplemental solar exchanger (connections S1 and S2).
The M3 connection without thermosiphonic separator is intended for the return connection of boilers that are to heat only the upper half of the buffer, or for the attachment of an electric heating element with a 6/4" outside thread.
The M4 connection is designed specifically for the return from the hot water tank. By means of the thermosiphonic separator, a warm return flows to the middle of the buffer and a cold return to the lower third.
The M6 and M7 connections are only installed on stratified buffers SP and SPS 2200. These connections are equipped with an inflow lance for high outputs with a flow rate of up to 20 m³/h.
If more than two buffers are used for hydraulic reasons, they must be connected using external piping in a Tichelmann system.
For the solar stratified buffer, a minimum collector area of 1 m² is required for each 100 litres. For smaller collector areas on larger buffers and very large solar heating systems, we recommend the
ETA stratified charging module.
Technical data | Unit | SP 600 SPS 600 | SP 825 SPS 825 | SP 1000 SPS 1000 | SP 1100 SPS 1100 | SP 1650 SPS 1650 | SP 2200 SPS 2200 |
---|
Volume | l | 600 | 825 | 1,000 | 1,100 | 1,650 | 2,200 |
Heat retention loss S* | W |
112,50 |
120,83 |
125,00 |
133,33 |
162,50 | - |
Tank classification* | | C | C | C | C | C | - |
Maximum permissible operating pressure | bar | 3 |
Maximum permissible operating temperature | °C | 95 |
Total weight (without solar exchanger) | kg | 117 | 141 | 160 | 166 | 274 | 328 |
Colour selection of the insulation | | Silver | Silver / melon yellow | Melon yellow |
I Insulation | mm | 100 |
d Diameter (without insulation) | mm | 700 | 790 | 790 | 850 | 1,000 | 1,150 |
D Diameter (with insulation) | mm | 900 | 990 | 990 | 1,050 | 1,200 | 1,350 |
H Height (with insulation) | mm | 1,800 | 1,939 | 2,219 | 2,150 | 2,370 | 2,380 |
K Tilted height (without insulation) | mm | 1,810 | 1,970 | 2,240 | 2,200 | 2,420 | 2,430 |
Position height | Unit | SP 600 SPS 600 | SP 825 SPS 825 | SP 1000 SPS 1000 | SP 1100 SPS 1100 | SP 1650 SPS 1650 | SP 2200 SPS 2200 |
---|
M0 | Coupling 6/4"
| top |
M1 | mm | 1,595 | 1,718 | 1,998 | 1,910 | 2,095 | 2,080 |
M2 | mm | 1,240 | 1,393 | 1,513 | 1,535 | 1,710 | 1,735 |
M3 | Coupling 6/4" (without shim) | mm | 865 | 833 | 943 | 940 | 1,020 | 1,100 |
M4 | Coupling 6/4" | mm | 800 | 773 | 883 | 875 | 940 | 965 |
M5 | mm | 125 | 148 | 148 | 170 | 205 | 230 |
M6 | 2" coupling | mm | - | - | - | - | - | 360 |
M7 | mm | - | - | - | - | - | 1,970 |
T1 | Immersion sleeve 9 mm diameter (for temperature sensor) | mm | 1,510 | 1,628 | 1,908 | 1,820 | 2,005 | 1,985 |
T2 | mm | 1,340 | 1,493 | 1,613 | 1,635 | 1,810 | 1,835 |
T3 | mm | 1,140 | 1,293 | 1,413 | 1,435 | 1,610 | 1,635 |
T4 | mm | 965 | 933 | 1,043 | 1,040 | 1,120 | 1,200 |
T5 | mm | 525 | 503 | 547 | 565 | 625 | 690 |
T6 | mm | 230 | 253 | 253 | 275 | 310 | 325 |
Supplemental data for Solar SPS stratified buffer:
Technical data | Unit | SPS 600 | SPS 825 | SPS 1000 | SPS 1100 | SPS 1650 | SPS 2200 |
---|
Optimum solar collector area (in relation to tank volume) | m² | 3-7 | 4-9 | 5-11 | 6-12 | 8-18 | 11-25 |
Maximum solar collector area
(as regards solar exchanger) | m² | 15 | 15 | 18 | 20 | 25 | 30 |
Maximum permissible operating pressure (solar exchanger) | bar | 16 |
Maximum permissible operating temperature (solar exchanger) | °C | 110 |
Total weight (with solar exchanger) | kg | 157 | 182 | 206 | 213 | 338 | 409 |
Heating area of solar exchanger | m² | 2.5 | 2.5 | 2.9 | 3.2 | 4.0 | 5.1 |
Volume of solar exchanger | l | 15.5 | 15.5 | 18.0 | 20.0 | 25.0 | 33.9 |
Pressure loss at 1000 l/h | mWs | 0.31 | 0.31 | 0.36 | 0.39 | 0.49 | 0.61 |
|
Position height | Unit | SPS 600 | SPS 825 | SPS 1000 | SPS 1100 | SPS 1650 | SPS 2200 |
---|
S1 |
R1“ coupling
(solar heat exchanger connection) | mm | 818 | 757 | 841 | 863 | 940 | 1.032 |
S2 | mm | 230 | 253 | 253 | 275 | 310 | 360 |
*The tank classification values specified by us for ETA SP/SPS and the heat retention losses apply only to the following combination:
ETA SP/SPS stratified buffer storage and insulation for ETA SP/SPS NeodulPlus
Just for the calculation of the energy labelling of packages - NOT VALID AS ENERGY EFFICIENCY FOR HOT WATER STORAGE TANKS
SP 3000 to 5000 stratified buffer
The number and position of the connections is optimised for the ETA hydraulics and control system. The following figures show an SP stratified buffer.
The M1 and M5 connections have a special inflow/outflow cylinder and are therefore designed for large boiler outputs up to 500 kW (25 m³/h).
The M3 connection without thermosiphonic separator is intended for the return connection of boilers that are to heat only the upper half of the buffer, or for the attachment of an electric heating element with a 6/4" outside thread.
The SP 3000–5000 tank range is only available without solar exchanger. For large volumes, a solar heating system is connected via external heat exchangers such as the ETA solar stratification module, for example.
The M4 connection is designed specifically for the return from hot water tanks.
If more than two buffers are used for hydraulic reasons, they must be connected using external piping in a Tichelmann system.
Technical data | Unit | SP 3000 | SP 4000 | SP 5000 |
---|
Volume | l | 3,000 | 4,000 | 5,000 |
Maximum permissible operating pressure | bar | 3 |
Maximum permissible operating temperature | °C | 95 |
Total weight (without solar exchanger) | kg | 397 | 477 | 582 |
Colour selection of the insulation | | Melon yellow |
I Insulation | mm | 100 |
d Diameter (without insulation) | mm | 1,250 | 1,400 | 1,600 |
D Diameter (with insulation) | mm | 1,450 | 1,600 | 1,800 |
H Height (with insulation) | mm | 2,712 | 2,920 | 2,850 |
K Tilted height (without insulation) | mm | 2,740 | 2,950 | 2,890 |
Position height | Unit | SP 3000 | SP 4000 | SP 5000 |
---|
M0 | Coupling 6/4" | mm | top |
M1 | 2" coupling | mm | 2,286 | 2,465 | 2,355 |
M2 | Coupling 6/4" | mm | 1,811 | 1,915 | 1,880 |
M3 | Coupling 6/4" (without shim) | mm | 1,176 | 1,300 | 1,245 |
M4 | Coupling 6/4" | mm | 1,041 | 1,145 | 1,110 |
M5 | 2" coupling | mm | 426 | 455 | 495 |
T1 | 9 mm immersion sleeve (for temperature sensor) | mm | 2,386 | 2,565 | 2,455 |
T2 | mm | 1,911 | 2,015 | 1,980 |
T3 | mm | 1,711 | 1,815 | 1,780 |
T4 | mm | 1,276 | 1,400 | 1,345 |
T5 | mm | 766 | 835 | 835 |
T6 | mm | 326 | 355 | 395 |